Momentum Modbus Plus 170 PNT Series Especificações Página 14

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 76
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 13
4/11Schneider Electric
4
Modbus Plus can be used as the fieldbus for a distributed I/O network under the control of a Quantum CPU. A Modbus
Plus master needs to reside at the head end of the network (as either a 140 NOM 21p module or Quantum CPU with a
built-in Modbus Plus interface). A 140 CRA 211 pp module must reside in each distributed I/O drop on the network. A
CRA module acts as both a distributed I/O adapter and a power supply for the drop; no additional power supply modules
are required. Each DIO drop can address up to 30 input words and 32 output words.
A single or redundant cable topology may be employed in the distributed I/O system. Depending on your system's
requirements, one of the following module combinations can be used to set up a Modbus Plus-based DIO system:
The Modbus Plus 140 NOMpp 00 modules at the end of the network comprise on the front panel:
1 Model number and color code
2 LED Status indicators comprising:
- Ready (green)
- Fault (red)
- Pwr ok (green)
- Modbus + (green)
- Error A (red)
- Error B (red)
3 Removable, hinged door with customer identification
label
4 Microswitch
5 Modbus port
6 Modbus Plus
Using Modbus Plus for distributed I/O
At the head At the drop Type of system
CPU with MBP or
140 NOM 211 00
140 CRA 211 10 Single cable with a 115/230 V power source at the drop
CPU with MBP or
140 NOM 211 00
140 CRA 211 20 Single cable with c 24 V power source at the drop
140 NOM 212 00 140CRA21110 Redundant cable with a 115/230 V power source at the drop
140 NOM 212 00 140CRA21120 Redundant cable with c 24 V power source at the drop
Description
Quantum automation platform 4
I/O architectures
Distributed I/O, Modbus Plus
Description
0
Vista de página 13
1 2 ... 9 10 11 12 13 14 15 16 17 18 19 ... 75 76

Comentários a estes Manuais

Sem comentários