Momentum Modbus Plus 170 PNT Series Especificações Página 9

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 76
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 8
4/6
Schneider Electric
4
Fiber optic repeaters are available to enhance network noise immunity and
increase cable distance to as much as 15 km (9.3 miles). Repeaters convert the
twisted-pair cable to standard 62.5/125 µm fiber while maintaining the full dynamic
range of the network.
Multiple 490 NRP 954 00 fiber optic repeaters can be interconnected in a closed loop
ring so that if a break occurs anywhere in the ring the network can reconfigure itself.
The RIO signal is sent down both legs of the ring by the drop repeater to the head
repeaters. When a signal is received on one Rx line, the other Rx channel is
blanked–this prevents the same signal from being transmitted twice in the ring. The
maximum length of fiber cable allowed in a self-healing ring is 10 km (32 000 ft).
Point-to-point RIO communications with fiber optic repeaters
Quantum head-end CPU with 140 CRP 931 00 adapter
Tap Tap
Tap with 52-0422-000
trunk terminator
RG-6 coax
drop cable
RG-11 coax
trunk cable
RIO drop 1 RIO drop 2 Last RIO drop
490 NRP 954 00
fiber optic drop
490 NRP 954 00
fiber optic drop
Fiber optic Rx and Tx cables
Tap with 52-0422-000
trunk terminator
RG-6 coax drop cable
RG-11 coax trunk cable
A self-healing ring topology
Quantum head-end
RIO drop 2
RIO drop 1
Terminated
tap
Terminated
tap
Terminated
tap
RIO drop 3
Repeaters
Repeater
Terminated
tap
RIO drop 4
Drop repeater
Repeater
Terminated tap
Quantum automation platform 4
I/O architectures
Remote I/O
Topologie (continued)
0
Vista de página 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 75 76