Configuring an M1 CPU with Modsoft
152
870 USE 101 00 V.2.2
Changing the Number of Segments
Introduction
The number of segments specified in the Configuration Overview screen
determines the number of I/O Map drops that you will be able to set up for your
CPU.
The number of segments you will need depends on whether your Processor
Adapter will support an I/OBus network.
For I/OBus
Networks
You must change the number of segments to 2 if you want to create an I/O Map to
support an I/OBus network.
For All Other
Cases
The default number of segments (1) is correct. You only need one drop because
the only points to be I/O Mapped are those on the local base.
Continued on next page