Using Peer Cop with Modsoft
870 USE 101 00 V.2.2
225
Specifying References for Input and Output Data,
Continued
Defining the
Global Inputs,
Continued
Next Step
Defining the references for the next node.
Step Action
4 Type the value
1
in the INDEX column of the GLOBAL INPUT field, indicating that
the the M1 CPU at Modbus Plus address 2 will receive the five words of global input
data beginning with word 1. Push
<Enter>
.
Result:
The Peer Cop screen is now set to send eight words of specific output to
the supervisor at Modbus Plus address 1 and receive five words of global data from
the supervisor. The screen should like this: