Using the Modbus Ports
870USE10110 July 2004 111
Port Parameters Modbus port 2 offers the following communication parameters.
Default
Parameters
The factory-set default communication parameters for Modbus Port 2 are:
9600 baud
EVEN parity
8-bit RTU mode
1 stop bit
Modbus network address 1
RS232 protocol
Baud 50 1800
75 2000
110 2400
134 3600
150 4800
300 7200
600 9600
1200 19,200
Parity EVEN
ODD
NONE
Mode/Data Bits 8-bit RTU
7-bit ASCII
Stop Bit 1
Modbus Address In the range 1 ... 247
Comm Protocol RS232
RS485
Note: Processor adapters support only one stop bit. If you change this default
setting in the configuration software, the processor adapter will ignore the change.
Note: The default protocol must be changed from RS232 to RS485 for the
171 CCS 780 00,171 CCC 780 10 processor adapters or the port will not
function.The 171 CCC 980 20 and 171 CCC 980 30 change automatically.