Configuring a Modbus Plus Network in Concept with Peer Cop
870USE10110 July 2004 323
Next Step Specifying output references (see p. 324).
3 Type the value 1 in the Length column, indicating that the device at address 2 will
exchange one word of data. In this case, we will leave the default BIN setting.
4 Repeat steps 2 and 3 for the device at address 4, using the settings in the figure
below. Then click <OK>.
Step Action
Range: 300001-300048 1-33
Specific Input
OK
Cancel
Help
Source Dest. Ref. Length Bin/BCD
1
2 300016 1 BIN
3
4
5
6
7
8
9
10
11
12
Range: 300001-300048 1-33
Specific Input
OK
Cancel
Help
Source Dest. Ref. Length Bin/BCD
1
2 300016 1 BIN
3
4 300017 2 BIN
5
6
7
8
9
10
11
12