Using the Ethernet Port
158
870USE10110 July 2004
Using BOOTP Lite to Assign Address Parameters for Momentum Components
Specifying
Addresses/
Stopping the
Processor
Instead of a BOOTP server, Schneider Electric’s BOOTP Lite utility software can be
used to provide the IP address, subnet mask and default gateway to the processor.
A response from BOOTP Lite will cause the processor to enter Stopped mode on
completion of power up, if the processor has been set to Specify IP Address mode
via Concept. This is useful when inappropriate outbound network traffic might result
if the processor immediately transitioned into Run mode after power up.
Refer to the BOOTP Lite user documentation for instructions.
UNINTENDED OPERATION – INCORRECT MAC ADDRESS
An incorrect MAC address may result in an unwanted change to another device or
cause unexpected results.
Enter the correct parameters of the target controller.
Otherwise, the controller runs on its old, or existing, configuration.
Verify the MAC address of the target device before invoking the Bootp Lite
Server Software.
Failure to follow this instruction can result in injury or equipment damage.
CAUTION
Note: BOOTP Lite and the user document are available for download at
www.modicon.com.