Configuring a Modbus Plus Network in Modsoft with Peer Cop
240
870USE10110 July 2004
Defining the
Global Inputs
Now the M1 needs to be Peer Copped to receive five words of global data from the
supervisory PLC at Modbus Plus address 1. Follow the steps in the table below to
specify the global input references.
3 In the LEN column of the SPECIFIC OUTPUT field, type the value 8, indicating that
the M1 CPU at address 2 will send eight 16-bit words to the supervisory PLC. Push
<Enter>.
Result: The Peer Cop screen should like this:
Step Action
Utility
GoToNode
AddNode OnError Quit
F1
F6
F7 Lev 8 F8 OFF F9F3 F4 F5
Timeout : 500 ms Total Links: Link Id:1
PEER COP
On Error : CLEAR USED 13 OF 2000 WORDS
REFERENCE LEN TYPE INDEXMODE
SPECIFIC INPUT -
SPECIFIC OUTPUT 400016-400023 8 BIN
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
F2
Timeout
Access to Node : 1
TO ALL NODES ON LINK
GLOBAL OUTPUT -
DelNode
Step Action
1 In the REFERENCE column on the first line of the GLOBAL INPUT field, type the
value 400001, the first register in which the CPU will store data. Push <Enter>.
Result: The cursor moves into the LEN column of the GLOBAL INPUT field.
Utility GoToNode AddNode OnError Quit
F1
F6
F7 Lev 8 F8 OFF F9F3 F4 F5
Timeout : 500 ms Total Links: Link Id:1
PEER COP
On Error : CLEAR USED 13 OF 2000 WORDS
REFERENCE LEN TYPE INDEXMODE
SPECIFIC INPUT -
SPECIFIC OUTPUT 400016-400023 8 BIN
GLOBAL INPUT 400001- BIN
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
F2
Timeout
Access to Node : 1
TO ALL NODES ON LINK
GLOBAL OUTPUT -
DelNode