Using the Modbus Ports
116
870USE10110 July 2004
Two-Wire Cabling Schemes for Modbus RS485 Networks Connecting
Momentum Components
Introduction Two-wire cabling schemes may be used for single master/slave or multimaster/
slave communications. Masters may be located anywhere in the network.
Length The maximum length of cable from one end of network to other is 2000 ft. (609 m).
Number of
Devices
The maximum number of devices in a network is 64 if all are Momentum devices.
Otherwise, the maximum is 32.
Termination One end of the cable run must be terminated with a terminating resistor (color code
is red).
The other end of the cable must be terminated with a terminating shunt, which
connects the transmit pair to the receiver pair (color code is blue).
Cable All devices are connected with the same pin-for-pin cable, such as the Modbus Plus
or Modbus RS485 short interconnect cable or any Cat. 5 4-twisted pair Ethernet
cable AWG#24. A master/slave system using 2-wire cabling does not require the
special master communication cable.
POTENTIAL FOR MULTIMASTER CONFLICTS
Conflicting messages to a slave module can cause problems.
Configure a multimaster network carefully to avoid masters issuing simultaneous or
conflicting commands to the same slave module.
Failure to follow this instruction can result in injury or equipment damage.
CAUTION
Description Part Number
Modbus Plus or Modbus RS485 terminating RJ45 resistor plugs (pack of 2) 170 XTS 021 00
Modbus RS485 terminating RJ45 shunt plugs 170 XTS 042 00
Description Part Number
Modbus Plus or Modbus RS485 short interconnect cable
Color code: black
170 MCI 020 10