Configuring a Modbus Plus Network in Modsoft with Peer Cop
226
870USE10110 July 2004
Specifying References for Input Data
(with Modsoft for a Modbus Network with Momentum Components)
Introduction The Peer Cop screen is now set to access the device at Modbus Plus address 2,
which for this example is a 170 ADI 340 00 16-point input module.
This section explains how to specify the reference for input data from this module.
Device
Requirements
When you use Peer Cop to handle a Modbus Plus I/O architecture, you need to be
aware of the type of I/O you are configuring at each network address. Peer Cop does
not know that the device at address 2 is a discrete 16-point input module.
You need to know that a specific input reference with a length of one word (16 bits)
is required to handle this module.
We will assign a 3x register (300016) as a specific input to the CPU. When the
170 ADI 340 00 sends input data to the CPU, it will be sent to this register.
Procedure Follow the steps in the table below to define the specific input in Peer Cop.
Step Action
1 Move the cursor to the REFERENCE column of the SPECIFIC INPUT field, using the
cursor arrow keys.
2 Type the value 300016 in the REFERENCE column of the SPECIFIC INPUT field,
then push <Enter>.
Result: The cursor moves into the LEN column of the SPECIFIC INPUT field.
Utility
GoToNode
AddNode OnError Quit
F1
F6
F7 Lev 8 F8 OFF F9F3 F4 F5
Timeout : 240 ms Total Links: Link Id:1
PEER COP
On Error : HOLD USED 1 OF 1366 WORDS
REFERENCE LEN TYPE INDEXMODE
SPECIFIC INPUT 300016- BIN
SPECIFIC OUTPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
F2
Timeout
Access to Node : 2
TO ALL NODES ON LINK
GLOBAL OUTPUT -
DelNode