Battery Life Information for Alkaline Batteries
870USE10110 July 2004 371
Power Cycling an
M1/M1E in a
Battery Low
Condition
If an earlier version of a Momentum Processor IEC or 984LL Exec. is being used,
the power cycle of a configured processor will force the processor to come up in a
Not Configured state if
the battery voltage is below the battery-low threshold level and
the program is not saved in Flash memory
Therefore, with earlier versions, the program must be reloaded to put the processor
back into Run mode.
Both IEC and 984LL Execs were updated to correct this issue of coming up Not
Configured. Therefore, now, when a battery-low threshold level is reached, the
processor will indicate only that the battery should be replaced within 30 days and
not force the processor into a Not Configured state.
Refer to the Exec. Resolution for further details.
The following table lists the Exec versions that resolve this issue of coming up Not
Configured:
Processor Exec Version
171CCS76000
171CCC78010
171CCC76010
M1 IEC 2.06
171CCS70000
171CCS70010
171CCS76000
171CCC76010
171CCC78000
171CCC78010
M1 984LL 2.05
171CCC96030
171CCC98030
M1E IEC 1.21
171CCC96020
171CCC96030
171CCC98020
171CCC98030
M1E 984LL 1.07