Configuring an M1 CPU with Concept
296
870USE10110 July 2004
Rep Rate Use this column to specify how often in ms to repeat the transaction. Valid values
are 0 ... 65,000 ms (1 min). To repeat the transaction continually, specify 0.
Read Use the read function to read data from the slave to the master. The Read Ref Slave
column specifies the first address to be read. The Read Length column specifies
the number of registers to read. The Read Ref Master column specifies the first
address to read to.
Write Use the write function to write data from the master to the slave. The Write Ref
Master column specifies the first address to write. The Write Length column
specifies the number of registers to write. The Write Ref Slave column specifies the
first address to write to:
Read and Write You may include read and write commands on the same line, as shown in the
preceding screen capture.
Description You can type a brief description (up to 32 characters) of the transaction in the
Description column.