Configuring an M1 CPU with Concept
286
870USE10110 July 2004
Changing the Delay on Modbus Ports
Overview The Delay parameter is set to 10 ms and should be left at this value for most
applications. Do not change this parameter unless your application demands it.
If you must change this parameter, you may select a value from 10 ... 1000 ms, in
10 ms increments.
Delay Timing If you use baud rates lower than 4800, adjust the delay timing as indicated in the
following table
Procedure Follow the steps in the table below to change the delay:
Baud Rate Delay (in ms)
2400 20
1200 30
600 50
300 100
Step Action
1 Click on the Delay parameter for the port.
2 Type a new value in the range 10 ... 1000 ms, using increments of 10 ms.