Configuring a Modbus Plus Network in Modsoft with Peer Cop
870USE10110 July 2004 249
Completing the Configuration of a Modbus Plus Supervisory Network with
Momentum Components (Using Modsoft)
Overview To complete the configuration of the supervisory computer at Modbus Plus address
1, create a Peer Cop screen that accesses the CPU at address 3 and defines the
references for that CPU.
Accessing
Node 3
Using the AddNode command, create a new Peer Cop screen with a Link setting of
1 and a Node setting of 3.
Specifying
References for
Node 3
We know that this M1 CPU sends 16 words of specific output to the supervisor and
receive seven words of global data from the supervisor. Follow the steps in the table
below to define the registers that the supervisor will transmit to and receive from the
M1 CPU at Modbus Plus address 3.
Step Action
1 In the REFERENCE column of the SPECIFIC INPUT field, type the value 400020,
the first register which will receive the input. Push <Enter>.
2 Type the value 16 in the LEN column of the SPECIFIC INPUT field, indicating the
number of registers that will be received. Push <Enter>.
3 The GLOBAL OUTPUT fields should already be complete, since you filled them out
for node 2. The completed Peer Cop screen should look like this:
Utility
GoToNode
AddNode OnError Quit
F1
F6
F7 Lev 8 F8 OFF F9F3 F4 F5
Timeout : 500 ms Total Links: Link Id:1
PEER COP
On Error : CLEAR USED 19 OF 2000 WORDS
REFERENCE LEN TYPE INDEXMODE
F2
Timeout
Access to Node : 3
TO ALL NODES ON LINK
Denude
SPECIFIC INPUT 400020-400035 16 BIN
SPECIFIC OUTPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL INPUT -
GLOBAL OUTPUT 400033-400042 10 BIN