Configuring an M1 CPU with Modsoft
190
870USE10110 July 2004
Setting the Time on Momentum Components in Modsoft
Overview Once you have reserved a block of registers for the time-of-day clock, you have to
set the correct time. Modsoft offers two ways to do this.
using the Set Hardware Clock dialogue
setting the register bits individually
Option 1 You must be online or in combined mode to access the Set Hardware Clock
dialogue.
Option 2 Go online and set the register values individually, using the following guidelines and
procedure for setting the status bits and setting the time bits. The CPU must be
running while you are setting the bits.
Note: The time-of-day clock complies with guidelines for the year 2000.
Step Action
1 From the PlcOps menu, select Set Hardware Clock.
The Set Hardware Clock dialogue appears.
2 You may set the time directly or copy the current time setting from your programming
panel.
To set the time directly, proceed to step 3.
To copy the setting from your programming panel, proceed to step 4.
3 The time setting for your programming panel is displayed on the left. The controller
time setting is displayed on the right. The time is expressed as hh:mm:ss. The date
is expressed as mm-dd-yy.
To modify the settings, type a new value in the date or time field for the controller.
To confirm the default settings or your modified settings, press <Enter>.
4 To copy the current time setting from your programming panel, type Y in response to
the question:
Write PANEL clock data to PLC? (Y/N). Then press <Enter>.